Steady State Error

Analyzing long-term accuracy in control systems

What is Steady State Error?

Definition: Steady state error (ess) is the difference between the desired output (reference input) and the actual output of a control system after all transients have died out and the system has reached equilibrium.

It represents the long-term accuracy of a control system and is a critical performance metric. A smaller steady state error indicates better tracking performance.

ess = limt→∞ e(t) = limt→∞ [r(t) - c(t)]

Where:

  • e(t) = Error signal at time t
  • r(t) = Reference input (desired output)
  • c(t) = Actual output

System Type

The system type is determined by the number of pure integrators (poles at the origin) in the open-loop transfer function:

G(s)H(s) = K · (s + z1)(s + z2)... / [sN(s + p1)(s + p2)...]

Where N is the system type (number of poles at s = 0).

System Type Poles at Origin Position Error Velocity Error Acceleration Error
Type 0 0 Finite ∞ ∞
Type 1 1 0 Finite ∞
Type 2 2 0 0 Finite
Type 3+ 3 or more 0 0 0

Error Constants

Error constants quantify steady state error for different input types:

1. Position Error Constant (Kp)

Kp = lims→0 G(s)H(s)

For step input: ess = 1 / (1 + Kp)

2. Velocity Error Constant (Kv)

Kv = lims→0 s·G(s)H(s)

For ramp input: ess = 1 / Kv

3. Acceleration Error Constant (Ka)

Ka = lims→0 s²·G(s)H(s)

For parabolic input: ess = 1 / Ka

Standard Test Inputs

Step Input: r(t) = A·u(t)

Laplace: R(s) = A/s

Represents: Sudden change in setpoint (e.g., thermostat adjustment)

Steady State Error:

  • Type 0: ess = A / (1 + Kp)
  • Type 1+: ess = 0

Ramp Input: r(t) = A·t·u(t)

Laplace: R(s) = A/s²

Represents: Constant velocity tracking (e.g., conveyor belt)

Steady State Error:

  • Type 0: ess = ∞
  • Type 1: ess = A / Kv
  • Type 2+: ess = 0

Parabolic Input: r(t) = A·t²·u(t)/2

Laplace: R(s) = A/s³

Represents: Constant acceleration tracking (e.g., missile guidance)

Steady State Error:

  • Type 0-1: ess = ∞
  • Type 2: ess = A / Ka
  • Type 3+: ess = 0

Calculation Using Final Value Theorem

The general formula for steady state error:

ess = lims→0 s·E(s) = lims→0 s·R(s) / [1 + G(s)H(s)]
Important: The Final Value Theorem is only valid if all poles of s·E(s) are in the left half of the s-plane (stable system).

Example Calculation

Problem

Given a unity feedback system with:

G(s) = 100 / [s(s + 5)(s + 10)]

Find the steady state error for a unit ramp input.

Solution

Step 1: Determine system type

One pole at origin → Type 1 system

Step 2: Calculate Kv

Kv = lims→0 s·G(s) = lims→0 100 / [(s + 5)(s + 10)]

Kv = 100 / (5 × 10) = 2

Step 3: Calculate ess

For unit ramp (A = 1): ess = 1 / Kv = 1 / 2 = 0.5

Result: The system will track a ramp input with a constant error of 0.5 units.

Reducing Steady State Error

1. Increase System Gain

Higher gain K reduces error but may affect stability

Trade-off: Stability margins vs. accuracy

2. Add Integrators

Increase system type by adding poles at origin

Integral control eliminates steady state error for certain inputs

3. Use PID Controller

Proportional-Integral-Derivative controller:

  • P: Reduces error magnitude
  • I: Eliminates steady state error
  • D: Improves transient response

4. Feedforward Compensation

Add feedforward path to anticipate disturbances

Reduces error without affecting feedback loop stability

Practical Applications

Temperature Control

Thermostat systems require zero steady state error for step inputs to maintain setpoint temperature accurately.

Motor Speed Control

DC motor controllers need Type 1 or higher to track varying speed commands without lag.

Robotic Positioning

High-precision robots require Type 2+ systems to track complex trajectories with minimal error.

Cruise Control

Automotive cruise control uses integral action to eliminate speed error on varying road grades.

Key Takeaways

Remember:
  • Steady state error measures long-term tracking accuracy
  • System type determines which inputs can be tracked perfectly
  • Higher system type = better tracking but potential stability issues
  • Error constants (Kp, Kv, Ka) quantify performance
  • Integral control (Type 1+) eliminates step input error
  • Use Final Value Theorem for calculation
  • Trade-off exists between error reduction and system stability